Air Conditioning Guide 2026 | Cooling Systems, Performance & Decarbonization | Wattnow
⚠️ Content copying is not allowed
Air Conditioning Guide – 2026 Edition

Master your
cooling systems
and decarbonize

Refrigeration cycle, performance indicators (COP, EER, IPLV), refrigerants, VRF technologies, energy audit and decarbonization.

30-60%
of the electricity bill in commercial buildings
−40%
savings via supervision
18 months
average IoT ROI
2027
GWP < 150 mandatory

Start
CHAPTER 1

Fundamentals of Air Conditioning

An air conditioning system is never a standard product

An air conditioning system is a set of components that cools, dehumidifies, filters and circulates air in a space to maintain occupant comfort during hot periods. Each installation is sized for a specific building and use. In France, the air conditioning load represents 30 to 60% of the electricity bill of a commercial building during the summer period.

7basic air treatment processes
3main refrigeration cycle families
4components of the vapor compression cycle

1.1 Comfort air conditioning, process air conditioning

In institutional, commercial and residential buildings, air conditioning systems primarily serve the health and comfort of occupants. This is referred to as comfort air conditioning. In industrial buildings, they serve the manufacturing process as well as operator comfort: this is process air conditioning. Cold rooms, on the other hand, address a third need: the preservation of foodstuffs.

Under these uses, three main technological families coexist. The choice between them depends on cost, the availability of a waste heat source and the target temperature.

Vapor Compression
  • The most widespread family (95% of installations)
  • Compressor circulates the refrigerant between high and low pressure
  • Technical foundation of air conditioners, chillers and heat pumps
  • Typical COP: 2.5 to 6.2 depending on technology
Vapor Absorption
  • Compressor replaced by a generator and an absorber
  • Relevant when a waste heat source is available
  • Higher initial investment cost but can be amortized
  • Uses pairs like ammonia-water or lithium bromide-water
Air Expansion
  • Reserved for niche applications
  • Aeronautics and cryogenics (very low temperature refrigeration)
  • Not common in standard building or industry

1.2 The seven basic air treatment processes

Regardless of the climate, any air conditioning system combines up to seven elementary operations. The local climate determines which ones are actually needed. In summer, the key processes are sensible cooling, dehumidification and air cleaning.

ProcessFunctionSummer priority
Sensible coolingRemoves heat from the conditioned spaceHigh
DehumidificationRemoves water vapor from the airHigh
Sensible heatingAdds heat to the conditioned spaceLow
HumidificationAdds water vapor to the airLow
Air cleaningRemoves dust, particles and contaminantsHigh
Air renewalExchanges air between inside and outsideHigh
Air movementControls air circulation in the spaceHigh

1.3 Components of an air handling unit

Behind every breath of conditioned air, a chain of components works in sequence. Understanding this chain means knowing where to look in case of performance drift.

Figure 1: Air treatment chain
From outdoor air to supply air Damper fresh air Mix fresh air + return Filter coil protection Coil hot Coil cold Humidifier water vapor Fan propulsion → Supply air Return air
📌 The most overlooked point of vigilance: a clogged filter increases the pressure drop throughout the system and degrades the performance of the downstream coils. Regular cleaning and replacement of filters is the most cost-effective maintenance action, and the most frequently postponed.
CHAPTER 2

Types of Systems & Thermal Comfort

Choose the right architecture, before choosing the equipment

Depending on the size, construction and intended operating mode, an air conditioning system belongs to one of five main families. Choosing the wrong architecture costs more than a bad brand choice.

2.1 Five architectures, five logics

Individual system
  • Window units, split or package air conditioners
  • Outdoor unit separate from indoor unit
  • Direct expansion (DX) cooling
  • Typical capacity: 2 to 15 kWf
  • Ideal for small spaces and residential
Evaporative cooling
  • Exploits cooling through water evaporation
  • No compressor, much lower consumption
  • Only effective in dry climates (humidity < 60%)
  • Energy savings: 50 to 80% compared to a conventional system
Thermal storage
  • Compressors operate during off-peak hours
  • Chilled water (4-6 °C) or ice stored for peak periods
  • Always centralized type
  • Reduces installed cooling capacity by 30 to 50%
Cleanroom
  • Critical particle control (ISO 14644)
  • Temperature, humidity, pressure, noise, vibrations
  • Directly impacts product quality (pharma, microelectronics)
  • ISO class 5 to 8 depending on needs
Why the central hydronic system changes the scale
Central hydronic system: chilled water distributed to multiple zones Thermal capacity of water ≈ 3,000 × that of air Heat transfer by water is more efficient than by air: ideal for large multi-zone buildings

2.2 Thermal comfort: a balance, not a temperature

Thermal comfort results from a heat balance between a person and their environment. Many parameters influence the feeling of comfort: activity (metabolism), ambient temperature and humidity, air movement, clothing. Comfort can be achieved at air temperatures between 20 °C and 26.6 °C, and relative humidity between 20% and 70%.

In summer, humidity control is crucial: excessively high relative humidity (> 70%) prevents sweating and worsens the feeling of heat. Effective dehumidification is therefore essential for summer comfort.

Psychrometric termDefinitionTypical summer value
Dry-bulb temperatureMeasured by a standard thermometer22-26 °C
Wet-bulb temperatureMeasured by a thermometer with a wet wick16-20 °C
Relative humidityRatio of actual water vapor / water vapor of saturated air40-60% RH
📌 Psychrometry is the common language of cooling: any sizing, regulation or audit decision is read on a psychrometric chart. Without mastering these concepts, it is impossible to correctly interpret a field measurement.
Exclusive content

The 6 chapters that turn reading into an action plan

Refrigeration cycle and performance indicators, quantified savings levers, refrigerants, VRF and chiller technologies, audit methodology and decarbonization.

Chapter 3: Refrigeration cycle & performanceCompressor, condenser, expansion valve, evaporator, COP, EER, IPLV
Chapter 4: Energy saving leversVAV, free-cooling, variable speed drives, chiller replacement
Chapter 5: RefrigerantsODP, GWP, CFC alternatives, absorption systems
Chapter 6: Advanced technologiesVRF, chillers, thermal storage, BMS
Chapter 7: Audit methodology & decarbonizationField checklist, low-carbon design
Chapter 8: FAQ & glossaryFrequently asked questions, expert lexicon
Immediate & free access

Reserved for building and industry professionals

Instant access: No credit card required

Access confirmed!

CHAPTER 3

Refrigeration cycle & performance indicators

The vapor compression refrigeration cycle powers the majority of air conditioning equipment. Understanding it is the key to interpreting a data sheet, a supervision alert or a performance discrepancy in the field.

Figure 2: Vapor compression refrigeration cycle
The 4 stages of the refrigeration cycle ① Compressor Isentropic compression 1 → 2 · LP vapor → HP Work = m(h2-h1) ② Condenser Isobaric condensation 2 → 3 · HP vapor → liquid Heat rejected = m(h3-h2) ③ Expansion device Isenthalpic expansion 3 → 4 · h3 = h4 · HP → LP Valve, capillary or thermostatic ④ Evaporator Isobaric evaporation 4 → 1 · absorbs heat Refrigerating effect = m(h1-h4) Key indicator: COP COP = (h1-h4) / (h2-h1) Refrigerating effect ÷ compression work Window/split: COP 2.5 to 3 Centrifugal: COP up to 6.2

3.1 Subcooling and superheat

The fluid leaving the condenser is generally subcooled below the saturation temperature, which increases the refrigerating effect. At the compressor suction, the vapor is slightly superheated to ensure dry compression. These two settings are performance levers.

  • Subcooling: the higher it is, the greater the refrigerating effect (typically 3 to 5 °C)
  • Superheat: typically 5 to 10 °C, protects the compressor from liquid slugging

3.2 Performance indicators

IndicatorFormulaUsageTypical value
COPRefrigerating effect (kW) ÷ input work (kW)Manufacturer's reference conditions2.5 to 6.2
EERRefrigerating effect (BTU/h) ÷ electrical power (W)Compressors, packages8 to 20
IPLV0.01·A + 0.42·B + 0.45·C + 0.12·DWeighted performance at 100/75/50/25% load3.5 to 8.5
kW/tonInput work (kW) ÷ refrigerating effect (ton)Consumption per ton of refrigeration0.4 to 2.0
IPLV = 0.01 × (100%) + 0.42 × (75%) + 0.45 × (50%) + 0.12 × (25%)
📌 Why IPLV matters more than nominal EER: equipment spends most of its time at partial load (between 40 and 80% load). IPLV reflects operational reality, not just full-load performance.

3.3 Three compressor families

Reciprocating (piston)
  • Capacity: 0.5 to 200 ton
  • Low initial cost, frequent maintenance
  • Ideal for small installations
Centrifugal
  • Capacity: 90 to 2,000 ton
  • Very efficient at full load, compact
  • Less efficient at partial load (except with inverter)
Screw
  • Capacity: 20 to 1,000 ton
  • Compact, lightweight, quiet
  • Efficient at both partial and full load
CHAPTER 4

Energy saving levers

An air conditioning system is custom-designed for a specific use: its audit is just as specific. The general methodology combines two complementary axes: reducing the load at source and optimizing operation.

Figure 3: Energy audit methodology
Two audit axes Verify capacity Reduce internal load Improve insulation Solar protection Inspection + maintenance Use a BMS Adjust setpoints Change filters + Real savings

4.1 CAV or VAV

A constant air volume (CAV) system always delivers the same air volume, regardless of the load. At partial load, it wastes energy by reheating the cooled air. A variable air volume (VAV) system delivers a variable air volume at constant temperature, significantly reducing waste. Converting a CAV fleet to VAV is a recognized energy saving measure, with typical gains of 20 to 40% on fan consumption.

4.2 Variable frequency drives (VFD)

📊 Example: 50 hp fan with VFD

A 50 hp fan operates 10 h/day, 250 days/year. At full speed, the annual cost is €5,559 (at €0.18/kWh). With a VFD and a realistic operating range (25% at 100%, 50% at 80%, 25% at 60%), the annual cost drops to €3,113.

€2,446annual savings
18-24 monthsreturn on investment
44%consumption reduction

4.3 Free-cooling

Free-cooling produces chilled water without running the compressor, by using cool outside air. In a data center in mainland France, free-cooling represents 50 to 75% of the annual time, i.e. 30 to 50% energy savings on cooling production.

  • Direct free-cooling: dedicated heat exchanger, chiller off
  • Indirect free-cooling: condenser cooling, chiller modulated
  • Integrated free-cooling: additional module on air-cooled chiller
📌 To remember: free-cooling is now a standard in data centers and large commercial buildings, no longer an option. It can be combined with thermal storage to further optimize consumption.

4.4 Replacing an existing chiller

📊 Replacement of an 800 kW chiller

An existing 800 kW chiller with an average seasonal COP of 3.5 is replaced by a chiller of the same capacity with an average seasonal COP of 4.5. Electricity cost: €0.18/kWh. Equivalent full-load operating hours: 1,000 h/year.

50,800 kWhenergy savings/year
€9,144financial savings/year
< 2.5 yearsreturn on investment

Before any replacement, five settings should be checked on the existing chiller:

  1. Set the chilled water to the highest possible temperature (increases COP)
  2. Lower the condensing water temperature (water-cooled condenser)
  3. Increase the heat exchange surface of the evaporator and condenser
  4. Enlarge refrigerant lines to reduce pressure drops
  5. Treat condensing water to prevent scaling
CHAPTER 5

Refrigerants & environmental impact

The refrigerant absorbs and transmits heat in the vapor compression cycle. Its decisive properties are the pressure-temperature relationship, chemical stability, toxicity, ozone depletion potential (ODP) and global warming potential (GWP).

RefrigerantFormulaODPGWP2026 status
CFC-12CF₂Cl₂110,600Banned
HFC-134aCH₂FCF₃01,300Phase-out in progress
HFC-152aCH₃CHF₂0120Promising alternative
HC-290 (propane)C₃H₈03Strong growth (limited charge)
HC-600a (isobutane)C₄H₁₀03Domestic refrigerators
R454BHFO/HFC0466Main transition 2024-2030
R1234zeHFO0< 1Long-term reference > 200 kWf
HFC-134a, the most common: requires hygroscopic synthetic oils, therefore stricter maintenance. Its GWP of 1,300 makes it less and less competitive compared to low GWP refrigerants like R454B or R1234ze.
PFAS uncertainty: a major strategic risk. HFOs (R1234ze, R454B) are classified as PFAS by OECD. The European restriction dossier could, in its strictest version, lead to the progressive ban of HFOs by 2027-2030. Must be considered now in any long-term planning.

5.1 Vapor absorption

The vapor absorption system is appealing for its low operating cost and environmental friendliness, as soon as a waste heat source is available (industrial waste heat, cogeneration, solar thermal). The compressor is replaced by a generator (desorber) and an absorber. The most commonly used pairs are:

  • Ammonia-water: for negative cooling, robust, but toxic
  • Lithium bromide-water: for positive cooling, safer, but requires a high generation temperature (80-120 °C)
CHAPTER 6

Advanced technologies: VRF, chillers & BMS

6.1 VRF: one outdoor unit, individualized needs

A variable refrigerant flow (VRF) system uses multiple evaporators of different capacities and configurations, enabling individualized comfort control, simultaneous heating and cooling according to zones, and heat recovery between zones. VRF saves 11 to 17% energy compared to conventional units.

Figure 4: Flexibility of a VRF system
One outdoor unit, five different needs Outdoor unit Variable speed compressor up to 48 indoor units Room A: 24 °C Room B: 18 °C Room C: 27 °C Room D: Off

6.2 Chillers (chilled water groups)

A chiller (chilled water group) is a thermodynamic machine that produces chilled water (5 to 18 °C) to supply cooling coils, radiant ceilings or process heat exchangers. It becomes essential when:

  • The capacity exceeds 100 kWf
  • Distribution distances are long (> 150 m)
  • Operation must be centralized
  • F-Gas requirements weigh on the DRV option

In 2026, the chiller market is marked by three converging transitions: refrigerant transition (low GWP), energy transition (partial load modulation) and digital transition (systematic IoT supervision).

6.3 BMS: the backbone of control

The building management system (BMS) monitors and regulates several systems at an optimal level: HVAC, electricity, security, maintenance. Protocols to impose in specifications:

  • BACnet/IP: for HVAC equipment (chillers, controllers)
  • Modbus RTU/TCP: for electricity meters and drives
  • MQTT + TLS: for cloud data collection
  • OPC UA: for integration with industrial systems
CHAPTER 7

Audit methodology & decarbonization

7.1 Field audit checklist

Operation & schedules
  • Reduce operation when space is unoccupied
  • Turn off unoccupied areas (vestibules, meeting rooms)
  • Adjust pre-cooling schedules
Setpoints & control
  • Adjust thermostats according to season (summer: 24-26 °C)
  • Calibrate them regularly
  • Install an enthalpy-based economizer cycle
Recovery & insulation
  • Heat recovery wheel: 50 to 70% energy recovered
  • Insulate ducts and chilled water pipes
  • Avoid thermal bridges
Basic maintenance
  • Clean coils
  • Replace filters (every 3-6 months)
  • Repair duct leaks

7.2 Decarbonization

Adopting decarbonization technologies can save 30 to 40% of a building's total energy. The priority levers for air conditioning are:

  • Free-cooling: maximum use of cool outdoor air
  • Natural refrigerants: R290 (propane), R744 (CO₂), R717 (ammonia)
  • Heat recovery: desuperheater for DHW
  • IoT supervision: continuous commissioning, drift detection
  • Thermal storage: load shifting to off-peak hours
🌱 Rule of thumb: A 1 °C decrease in condensing temperature improves COP by 2 to 4%. A 1 °C increase in evaporating temperature improves COP by 2 to 4%. In summer, these two levers are crucial for maintaining efficiency.
CHAPTER 8

FAQ & glossary

FAQ

COP, EER or IPLV: which one to look at first? IPLV weights performance at 100/75/50/25% load: it is the most representative indicator of actual operation, as equipment spends most of its time at partial load.
VAV or CAV for a new project? VAV minimizes waste at partial load. Retrofitting an existing CAV system to VAV is generally cost-effective, with 20 to 40% gains on fans.
When to replace a chiller? Check the basic settings (water temperature, condensation). If the seasonal COP remains low compared to a newer unit (COP 4.5+), the ROI is typically between 2 and 5 years.
Which refrigerant to choose in 2026? R454B or R1234ze depending on capacity and manufacturer. Anticipate PFAS by prioritizing natural refrigerants (R290, R744, R717) on long-term projects.
What is the ROI for IoT supervision? 18 to 36 months in average commercial buildings, 6 to 18 months in critical sites (data center, hospital). Covered by 15 to 40% of Energy Savings Certificates.

Glossary

  • COP: Coefficient of Performance = Refrigerating effect ÷ compression work
  • EER: Energy Efficiency Ratio = Refrigerating effect (BTU/h) ÷ electrical power (W)
  • IPLV: Integrated Part Load Value: Weighted performance at 100/75/50/25% load
  • ODP: Ozone Depletion Potential
  • GWP: Global Warming Potential
  • CAV: Constant Air Volume
  • VAV: Variable Air Volume
  • VRF: Variable Refrigerant Flow
  • BMS: Building Management System
  • Free-cooling: Cooling production without a compressor using outside air
  • Subcooling: Liquid cooled below its saturation temperature
  • Superheat: Vapor heated above its saturation temperature
  • Dry bulb / wet bulb: Temperatures measured with and without a wet wick
❄️

Move to the energy audit of your air conditioning

Refrigeration cycle, performance indicators, quantified savings levers: this guide gives you the method. Our teams can support you in implementing it on your installation.

Book a demo now